LC1-D0910 Contactor Telemecanique Electrical Circuit Line 220V 9A 50Hz for AC Motor 690V insulate class is mainly composed of four parts:
(1) the electromagnetic system, including attracting coil, a movable iron core and the static iron core,
(2) the contact system, which comprises three groups of main contact and one to two groups of normally open, normally closed auxiliary contact and the moving iron core, it is together mutual linkage,
(3) out AC contactor arc device, generally larger capacity is provided with an arc extinguishing device, in order to quickly cut off from the main contact arc, burnt out,
(4) insulation casing and accessories, all kinds of spring, a transmission mechanism, a short circuit ring, terminal etc..
LC1-D0910 Contactor Telemecanique Electrical Circuit Line 220V 9A 50Hz for AC Motor 690V insulate class Main technical data
Type
LC1-D09
LC1-D12
LC1-D18
LC1-D25
LC1-D32
LC1-D40
LC1-D50
LC1-D65
LC1-D80
LC1-D95
Rated working current(A)
380V
AC-3
9
12
18
25
32
40
50
65
80
95
AC-4
3.5
5
7.7
8.5
12
18.5
24
28
37
44
660V
AC-3
6.6
5.9
12
18
21
34
39
42
49
55
AC-4
1.5
2
3.5
4.4
7.5
9
12
14
17.3
21.3
Conventional thermal current(A)
20
20
32
40
50
60
80
80
125
125
Power of controllable three-phase squirrel cage motor AC-3 (KW)
220V
2.2
3
4
5.5
7.5
11
15
18.5
22
25
380V
4
5.5
7.5
11
15
18.5
22
30
37
45
660V
5.5
7.5
9
15
18.5
30
33
37
45
55
Type
LC1-D115
LC1-D150
LC1-D170
LC1-D205
LC1-D245
GMC-300
GMC-410
GMC-475
LC1-D620
Rated working current(A)
380V
AC-3
115
150
170
205
245
300
410
475
620
AC-4
52
60
75
85
105
217
135
147
180
660V
AC-3
86
107
110
130
170
325
305
355
460
AC-4
49
61
69
80
90
118
135
145
170
Conventional themal current(A)
250
250
250
275
315
400
500
700
1000
Power of controllable three-phase squirrel cage motor AC-3 (KW)
220V
30
40
55
63
72
100
110
147
200
380V
55
75
90
110
132
160
200
265
335
660V
80
100
110
129
160
220
280
335
450
MatchFuse model
RT16-160
RT16-250
RT16-250
RT16-315
RT16-315
RT16-400
RT16-500
RT16-630
RT16-630
Conform to standard
GB/T14048.1 GB14048.4 IEC60947-4-1
Electrical life time:
1200~300 time
Machinical life time
3600~2400 times